Siemens S7 PLC¶
The foglamp-south-s7 plugin is a south plugin that reads data from a Siemens S7 PLC using the S7 communication protocol. Data can be read from a number of sources within the PLC
Data blocks - The data blocks store the state of the PLC
Inputs - Read the state of the inputs to the PLC
Outputs - Read the state of the outputs from the PLC
Merkers - Read from the single bit flag store
Counters - Read a counter
Timers - Read a timer
Note
If using an S7-1200 or S7-1500 PLC and the Optimized block access option for a data block is checked, the plugin is unable to read items within that block as they are no longer at fixed offsets within the block. If this option is checked we recommend using OPC UA to access the items within this block. If this is not an option then you must turn off the Optimized block access and rebuild your PLC code.
Configuring the PLC¶
There are a number of configuration steps that must be taken on the PLC itself to support the use of the S7 protocol.
Assigning an IP Address¶
Using the Siemens TIA console assign an IP address to your PLC. Connect to your PLC and locate the display of the PLC device. Double click on the network connector to bring up the properties for the network interface.
Assign an IP address to your interface and if you require it you may also assign a router to use.
Enable PUT/GET operations¶
The S7 1200 and 1500 series PLC’s require the PUT/GET communication from partners to be enabled in order to retrieve data using the S7 protocol. To permit the PUT/GET network operations on your PLC use the Siemens VIA tool. Note you must be sure that you are offline when you do this. Locate you PLC in the tool and right click on the device select properties and the following dialog will be displayed.
The older S7-300 and S7-400 series do not require this to be done.
Select the protection tab and scroll down to find the checkbox that enables the use of GET/PUT operations. Make sure it is selected for your PLC.
Using the Plugin¶
To create a south service with the Siemens S7 plugin
Click on South in the left hand menu bar
Select S7 from the plugin list
Name your service and click Next
Configure the plugin
Default Asset Name: The name of the asset to use if none is given in each of the data mapping items.
PLC IP Address: The IP address assigned to your PLC.
Rack: The rack number to address, usually this is 0 for a standalone PLC.
Slot: The slot within the rack, most CPU’s are in slot 1 of the rack.
Map: The data mapping for the plugin. This tells the plugin what data to fetch from the PLC.
Map Format¶
The data mapping uses a JSON document to define the data that should be read. The document is an array of items to read from the PLC, each item is a datapoint within either the default asset or it may be defined as a different asset within the item. An item contains a number of properties
asset: An optional property that can be used to put this item into an asset other than than one defined as the default asset for the service.
datapoint: The name of the data point that the data will be placed in. All items must have a datapoint defined.
area: The area in the PLC that data will be read from. There are a number of areas available
PE: Process Input - these are the inputs to the PLC
PA: Process Output - these are the outputs from the PLC
MK: Merker - a single bit memory used to store flags
DB: Data Block - the data blocks within the PLC used to store state within the PLC code
CT: Counter - The counters within the PLC
TM: Timer - The timers within the PLC
You may use the abbreviated area name, e.g. PA or the longer name Process Inputs interchangeably in the map.
DBnumber: The data block number, this is only required for data blocks and is used to define the block to read.
start: The offset of the start of the item within the data block
type: The type of the data item to read. A number of different types are supported
bit: A single bit value, mostly used to retrieve the state of a digital input to the PLC.
Note
When the type is set to bit then the start becomes a bit offset rather than a byte offset. Multiply the offset shown in the PLC by 8 and then add the bit number to obtain the right bit within the bit. For example if the PLC shows the bit a address 20 in the database segment then multiply this value by 8, to give 160 and then to read bit 1 within this location simply add 1 to give a start value of 161.
byte: A 8 bit integer value.
word: A 16 bit integer value.
int: A 16 bit signed integer value.
dword: A 32 bit integer value.
dint: A 32 bit signed integer value.
real: A 32 bit floating point value.
counter: A 16 bit counter.
timer: a 16 bit timer.
Note
Although shown here with the type names all in lower case, the plugin will accept any case for the type names. Also the abbreviated area names may be specified in any case. Longer area names require correct capitalisation.
A simple data mapping that wanted to read the state of two digital inputs to the PLC, say DI0 and DI2, and wanted to label these as datapoints “Stop” and “Start” within the default asset would consist of two items as follows
{ "items" : [ { "datapoint": "Stop", "area": "PE", "start": 0, "type": "bit" }, { "datapoint": "Start", "area": "PE", "start": 2, "type": "bit" }, ] }
In this case we set start to 0 for DI0 as it is the first digital input in the set. DI2 has a start of 2 as it is the second input. We use the type of bit to return a simple 0 or 1 to indicate the state of the input. We could use byte instead, this would return the 8 inputs states encoded as a binary number.
{
"datapoint": "Inputs",
"area": "PE",
"start": 0,
"type": "byte"
}
Since start is set to 0 and type is byte, then we return the state of the 8 inputs. We can do the same thing using the longer name form of the area as follows.
{
"datapoint": "Inputs",
"area": "Process Inputs",
"start": 0,
"type": "byte"
}
To add in a digital output, say DO4 and label that running, we would add another item to the map
{
"datapoint": "Running",
"area": "PA",
"start": 4,
"type": "bit"
}
If we assume we have a data block that we wish to read data from that appears as follows
Then we can setup a number of items in the map to retrieve these values and place them in data points. The items that would read this data block would be
{
"datapoint": "count",
"area": "DB",
"DBnumber" : 1,
"start": 0,
"type": "word"
},
{
"datapoint": "state",
"area": "DB",
"DBnumber" : 1,
"start": 2,
"type": "word"
},
{
"datapoint": "failures",
"area": "DB",
"DBnumber" : 1,
"start": 4,
"type": "dword"
},
{
"datapoint": "rate",
"area": "DB",
"DBnumber" : 1,
"start": 8,
"type": "word"
},
{
"datapoint": "running",
"area": "DB",
"DBnumber" : 1,
"start": 12,
"type": "word"
},
{
"datapoint": "downtime",
"area": "DB",
"DBnumber" : 1,
"start": 14,
"type": "timer"
}
For clarity we have used the name in the data block as the datapoint name, but these need not be the same.
If there is an error in the map definition for a given item then that item is ignored and a message is written to the error log. For example if a bad area name is given
Jun 25 08:53:04 foglamp-18 FogLAMP S7[6121]: ERROR: Invalid area Data specified in device mapping for S7 db1-bad
Jun 25 08:53:04 foglamp-18 FogLAMP S7[6121]: ERROR: Discarded invalid item in map for datapoint db1-bad
If a Data Block is missing it’s DBnumber property then the following style of error will be produced.
Jun 25 08:39:07 foglamp-18 FogLAMP S7[6121]: ERROR: Missing data block number in map for S7, db1-bad. A data block number must be specified for a data block area read.
Jun 25 08:39:07 foglamp-18 FogLAMP S7[6121]: ERROR: Discarded invalid item in map for datapoint db1-bad
Other errors that can occur include
Jun 25 08:57:28 foglamp-18 FogLAMP S7[6121]: ERROR: Missing start in map for datapoint db1-bad
Jun 25 08:57:46 foglamp-18 FogLAMP S7[6121]: ERROR: Missing type in map for datapoint db1-bad
See Also¶
foglamp-filter-breakover - Filter to forecast the possibility of a breakover.
foglamp-south-ABB - A south plugin to pull data from the ABB cloud
foglamp-south-Beckhoff - A Beckhoff ADS data ingress plugin for FogLAMP, this monitors Beckhoff PLCs and returns the state of internal variables within the PLC
foglamp-south-ModbusC - A FogLAMP south plugin that implements modbus-tcp and modbus-rtu
foglamp-south-dnp3 - A south plugin for FogLAMP that implements the DNP3 protocol
foglamp-south-etherip - A south plugin to read tags data from a number of different Allen-Bradley and Rockwell PLCs.
foglamp-south-opcua - A FogLAMP south service that pulls data from an OPC-UA server
foglamp-south-s2opcua - An OPC UA south plugin based on the Systerel S2OPC OPC UA Toolkit. This plugin offers similar functionality to the foglamp-south-opcua plugin but also offers data encryption and authentication.